Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T21CM06612
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/16/2021 | PCAMARE1 | OIP | REVIEW | Reqs Change | PROJECT: T21CM06612 Roof top Solar Panels 9678 E SASCHA ST TRANSMITTAL DATE: November 16, 2021 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Residential Review Section comments were addressed. COMMENT: Residential has reviewed the plan and cannot approve at this time. Please address the following comments These comments were not addressed COMMENT: The Plan Set shows a line-side tap, Line taps require compliance with NEC 230.46 and maintain UL listing. Update the plans showing a tap enclosure with sufficient space for the tap device.or show a meter socket extension with tap terminals (approved Milbank tapping device). Exiting panel COMMENT: On sheet number PV-5, clarify if the main service panel is existing or if a new main service panel. COMMENT: Residential will review the application on the next submittal If you have any questions about this transmittal, Contact Paul Camarena any time during the week by email Paul.camarena@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
11/17/2021 | NGARCIA3 | OUT TO CUSTOMER | Completed |