Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T21CM06612
Parcel: 136089550

Address:
9678 E SASCHA ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM06612
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/02/2021 PCAMARE1 OIP REVIEW Reqs Change PROJECT: T21CM06612
Roof top Solar Panels
9678 E SASCHA ST

TRANSMITTAL DATE: November 2, 2021



COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Residential Review Section comments were addressed.


COMMENT: Residential has reviewed the plan and cannot approve at this time. Please address the following comments


These comments were not addressed
COMMENT: The Plan Set shows a line-side tap, Line taps require compliance with NEC 230.46 and maintain UL listing. Update the plans showing a tap enclosure with sufficient space for the tap device.

COMMENT: On sheet number PV-5, clarify if the main service panel is existing or if a new main service panel.


COMMENT: Residential will review the application on the next submittal


If you have any questions about this transmittal, Contact Paul Camarena any time during the week by email Paul.camarena@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans