Permit Number: T21CM06585
Parcel: 11619227A

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T21CM06585
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/30/2021 JPEELDA1 FIRE REVIEW Approved
09/07/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. General: When applying for a damage repair permit where the repair materials are like-for-like to the damaged materials, the requirements for the permit submittal are as follows:
A) A site plan indicating the damaged building location, and specifically locating the damaged areas to be replaced or repaired.
B) A short narrative on this drawing indicating a project description and the extent of the repairs.
C) A valuation for the project (labor + materials).
2. The site plan provided does not require a registered design professional (architect or engineer) to seal, sign, and date that plan as long as repairs include like-for-like materials. If different construction materials are used, or the existing configuration of materials is changed from the original, then the drawing and documents will require a registered design professional to seal, sign, and date the drawings.
09/16/2021 LOREN MAKUS ENGINEERING REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
09/17/2021 VVERA1 OUT TO CUSTOMER Completed