The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T21CM06543
Parcel: 131040560

Address:
4951 E 24TH ST

Review Status: Completed

Review Details: OTHER

Permit Number - T21CM06543
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/07/2021 PCAMARE1 OIP REVIEW Reqs Change FROM: Paul Camarena
PDSD Zoning Review Section

PROJECT: T21CM06543
Rooftop Solar Panels (1st Review)
4951 E 24Th ST

TRANSMITTAL DATE: September 7, 2021



COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


• COMMENT: Zoning has reviewed the plan and cannot approve it at this time. Please address the following comments.

• COMMENT: After comparing the aerials to the plot plan it has come to my attention that there is a possible non-permitted garage addition on the East portion of the house. After researching PRO there were no records for the garage addition that could be verified or found. If no permits are available relocate the solar panel away from the garage structure or a permit must be obtained for the garage addition.


• COMMENT: Zoning will review the application on the next submittal




If you have any questions about this transmittal, Contact Paul Camarena any time during the week by email Paul.Camarena@Tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans

Final Status

Task End Date Reviewer's Name Type of Review Description
09/07/2021 NGARCIA3 OUT TO CUSTOMER Completed