Permit Number: T21CM06502
Parcel: 125101380

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM06502
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/15/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change The resubmitted exterior lighting plans did not provide enough information to verify full compliance with the 2012 Outdoor Lighting Code. Please provide the following information; Provide plans and evidence on the plans that the proposed exterior lighting fully complies with the Outdoor Lighting Code. See section 104 for plan submittal requirements.

Provide lighting plans with the following information on the plans;

Provide a complete luminaire schedule.

Size of the parcel in acres.

See table 401.1, lighting area and option and indicate this information in the lighting site plan, also showing the locations and types of all exterior luminaires including existing.

(d) 402.1 (light source color temperature requirements), shielding requirements, etc .

(e) Provide calcs for total lumens allowed and total lumens proposed per acre including existing, for Full Cut Off and Unshielded per table 401.1.

(f) Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2.

(g) Specify any exceptions used.

(h) Curfew lighting controls If applicable.

Do not confuse the Outdoor Lighting Code with the IECC.

Ref; 2017 NEC, 2012 Tucson/Pima County Outdoor Lighting Code (OLC), 2018 IBC sec 107.2.1. 2018 IECC. Be advised, if the under canopy luminaires have full cut off shielding and color output lamp temperatue does not exceed 3500K, then the proposed canopy lighting is exempt from meeting the lumen Cap per table 401.1.
12/21/2021 STEVE SHIELDS ZONING REVIEW Approved
12/21/2021 SSHIELD1 ENGINEERING REVIEW Approved