Permit Number: T21CM06502
Parcel: 125101380

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM06502
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/20/2021 JVINCEN1 FIRE REVIEW Approved
08/23/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
08/25/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
08/25/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
08/25/2021 ROBERT SHERRY WATER REVIEW Completed
08/31/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM06502
3605 E Broadway Blvd – Chick-Fil-A
Exterior canopy – C-1/C-2

TRANSMITTAL: August 31, 2021

This site is located in the C-1/C-2 zone (UDC 4.7.20/ 4.7.21). Food Service is a permitted use in this zone (Table 4.8-4).

1. As you are proposing an exterior structure, a Development Package (DP) meeting the requirements of the Checklist for Minor Changes to Commercial/Industrial Sites must be submitted and approved. The checklist can be found at: https://www.tucsonaz.gov/files/pdsd/forms/Minor_Changes_to_Commercial_Industrial_Sites_.pdf.
A DP is a separate submittal from the building permit and is submitted at: https://docs.tucsonaz.gov/Forms/tucsonpermitapp, using the “Submission Type”, “Site Review”.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.
08/31/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/01/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments also provide a written response.

Provide full compliance with the 2012 Tucson/Pima County Outdoor Lighting Code for the exterior lighting.. See section 104 for plan submittal requirements.

Ref; 2018 IBC 107.2.1, 2017 NEC, 2018 IECC, 2012 Tucson/Pima County Outdoor Lighting Code, City of Tucson Commercial Plan Submittal Requirements.
09/16/2021 SBLOOD1 ENGINEERING REVIEW Reqs Change See Zoniing comments