Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T21CM06492
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/11/2021 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T21CM06492 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Denied 1. It appears that special inspections will be required. Provide all special inspection information per Chapter 17 BUILDING REVIEW COMMENTS: Denied 1. Provide an existing floor plan. No existing floor plan provided 2. No egress plan provided. Provide a detailed egress plan. 3. Provide an update comcheck for the building envelope. MECHANICAL REVIEW COMMENTS: Approved ELECTRICAL REVIEW COMMENTS Approved PLUMBING REVIEW COMMENTS: Approved |
| 08/25/2021 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 08/30/2021 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 08/30/2021 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
| 08/30/2021 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 08/31/2021 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Show the location of the proposed water meter, backflow preventer, and the water service pipe on a site plan (e.g. civil site plans referenced on sheet P1.1). The development package is not a substitute for a complete site plan. Reference: Section 107.2.1 and 107.2.6, IBC 2018. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/01/2021 | NGARCIA3 | OUT TO CUSTOMER | Completed |