Permit Number: T21CM06492
Parcel: 13405119P

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T21CM06492
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/11/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM06492

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
Denied
1. It appears that special inspections will be required. Provide all special inspection information per Chapter 17
BUILDING REVIEW COMMENTS:
Denied
1. Provide an existing floor plan. No existing floor plan provided
2. No egress plan provided. Provide a detailed egress plan.
3. Provide an update comcheck for the building envelope.
MECHANICAL REVIEW COMMENTS:
Approved
ELECTRICAL REVIEW COMMENTS
Approved
PLUMBING REVIEW COMMENTS:
Approved
08/25/2021 JPEELDA1 FIRE REVIEW Approved
08/30/2021 STEVE SHIELDS ZONING REVIEW Approved
08/30/2021 SSHIELD1 ENGINEERING REVIEW Passed
08/30/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/31/2021 ROBERT SHERRY WATER REVIEW Reqs Change Show the location of the proposed water meter, backflow preventer, and the water service pipe on a site plan (e.g. civil site plans referenced on sheet P1.1). The development package is not a substitute for a complete site plan. Reference: Section 107.2.1 and 107.2.6, IBC 2018.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/01/2021 NGARCIA3 OUT TO CUSTOMER Completed