Permit Number: T21CM06488
Parcel: Unknown

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T21CM06488
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/23/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM06488

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
Approved

BUILDING REVIEW COMMENTS:
Denied
1. The exit the travels through the stockroom is required to comply with section 1016.2 #5 Exception #2. Show compliance with all requirements for exiting through stockroom in Mercantile occupancies.
2. Provide clarification on the adjacent tenant space, if there is one. Ensure the demising walls meet the requirements of Section 508.

MECHANICAL REVIEW COMMENTS:
Approved

ELECTRICAL REVIEW COMMENTS
Approved

PLUMBING REVIEW COMMENTS:
Approved
08/25/2021 LOREN MAKUS ENGINEERING REVIEW Passed
08/30/2021 STEVE SHIELDS ZONING REVIEW Approved
08/30/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/07/2021 ROBERT SHERRY WATER REVIEW Completed
09/08/2021 JVINCEN1 FIRE REVIEW Reqs Change -Second exit from showroom main cannot pass through a storage room unless all exceptions of 1016.2 #5, exception #2 are met.
-Indicate if a fire alarm is installed in building.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/08/2021 NGARCIA3 OUT TO CUSTOMER Completed