Permit Number: T21CM06486
Parcel: 13624450A

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T21CM06486
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/04/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Previous Comment 3; Sheet G001; Code Analysis Summary (Dead End Corridors): Please revise the Corridor Length to indicate "Shall not exceed 20 feet".
2. Previous Comment 5; Sheet A500; General Notes (Note 10): New note 13 references Sheet A501 for partition wall bracing. This sheet was not included in this submittal set. Please provide.
3. General: The new submittal set must include all drawings as listed in the Project Drawing Sheet List on Sheet G000. Please provide.
10/11/2021 ROBERT SHERRY WATER REVIEW Completed
10/11/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Comment not resolved. The specified lavatory faucets are not metering faucets, the specification is unchanged from the initial submittal. [Initial comment: Provide metering faucets for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10-seconds. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.]
10/13/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
10/21/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved