Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T21CM06486
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/04/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Previous Comment 3; Sheet G001; Code Analysis Summary (Dead End Corridors): Please revise the Corridor Length to indicate "Shall not exceed 20 feet". 2. Previous Comment 5; Sheet A500; General Notes (Note 10): New note 13 references Sheet A501 for partition wall bracing. This sheet was not included in this submittal set. Please provide. 3. General: The new submittal set must include all drawings as listed in the Project Drawing Sheet List on Sheet G000. Please provide. |
10/11/2021 | ROBERT SHERRY | WATER | REVIEW | Completed | |
10/11/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Comment not resolved. The specified lavatory faucets are not metering faucets, the specification is unchanged from the initial submittal. [Initial comment: Provide metering faucets for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10-seconds. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.] |
10/13/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
10/21/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |