Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T21CM06486
Parcel: 13624450A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM06486
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/19/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet G001; Building Plan: The plan indicates an occupant load of 58 at each exit. Each exit should indicate only the occupant load that would use that exit, and the total sum for the three exits should be 58. Please revise.
2. Sheet G001; Code Analysis Summary (Corridors): Per the IBC Table 1020.1, a corridor serving an occupant load of 30 or less does not require a fire resistance rating where there is no automatic sprinkler system. Please indicate all corridors meet that criteria.
3. Sheet G001; Code Analysis Summary (Corridors): Dead end corridors (although not applicable to this project) indicate on the drawings that they shall not exceed 50'. Per the IBC Section 1020.4, dead end corridors shall not exceed 20' in length in unsprinklered buildings. Please revise.
4. Sheet A500; Sheet Legend Partition Types: Please indicate the gauge of all studs listed, or provide a reference for that information.
5. Sheet A500; General Notes: Please provide a detail on the drawings for Note 10, indicating the bracing size, gauge, and the connection of the bracing to the top of the partition and to the structure above (include connection size and quantity).
6. General: Please provide a valuation (labor + materials) for this project. That number was listed as $1.80 in the application.
7. General: Please provide a Special Inspections Certificate with Parts A and B completed. This should include masonry and epoxy anchors.
8. General: Please provide written responses to all review comments.
08/20/2021 JVINCEN1 FIRE REVIEW Approved
08/24/2021 ROBERT SHERRY WATER REVIEW Reqs Change 1. The submitted water pressure analysis is based on an assumed pressure of 60 PSI. According to Tucson Water, the water pressure at this address has a range of 40 to 47 PSI. Include the static lift in the calculations.
2. Provide the size of the water meter serving this suite, the size of the backflow preventer associated with the water meter, and the total water demand served by the water meter. Reference: Section 107.2.1, IBC 2018.
3. Detail 221113.00-01/P501 is not correct for this activity. Reduced pressure backflow prevention assemblies are required to be installed in locations accessible to Tucson Water. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf
08/25/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Revise the hot water supply to the restroom lavatories so that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018.
2. Provide metering faucets for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10-seconds. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
3. Verify that the pipe sizes called out for the flush valves will not result in water velocities greater than that recommended by the pipe manufacturer (e.g. limit the water velocity to less than 8 FPS for copper, PEX, or CPVC piping). At a minimum design flow rate of 25 GPM for a siphonic, flush-valve water closet, a 1” Type L copper pipe has a flow velocity of 9.7 FPS. Reference: Table 604.3, IPC 2018.
Provide a complete diagram of the natural gas distribution system showing all of the loads, developed lengths, and the layout of the distribution piping. Reference: Section 402.2, IFGC 2018.
08/25/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. The occupancy classification of this suite is B (business), not I-2. Provide ventilation per Section 403.3.1, IMC 2018.
2. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Section 6.4.2.1, ASHRAE 90.1-2016.
3. Provide the sequence of operation for EF-1 and EF-3. Reference: Section 107.2,1, IBC 2018.
08/31/2021 STEVE SHIELDS ZONING REVIEW Approved
08/31/2021 SSHIELD1 ENGINEERING REVIEW Passed
08/31/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments also provide a written response.

Provide electrical plans that are Sealed by a Registrant registered in the State of Arizona.

Ref; 2018 IBC 107.2.1, 2017 NEC, 2018 IECC, 2012 Tucson/Pima County Outdoor Lighting Code, City of Tucson Commercial Plan Submittal Requirements.
08/31/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed