Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T21CM06478
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/07/2021 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | FROM: PDSD Zoning Review PROJECT: T21CM06475 3035 N Los Altos Ave – R-2 Convert Storage to Studio TRANSMITTAL DATE: August 24, 2021 This site is located in the R-2 zone (UDC 4.7.9). Multi-family residential is a permitted use in this zone (Table 4.8-2). See Use Specific Standards 4.9.7.B.6, .9 & .10. Perimeter yard setbacks are based on a measurement from design grade to the highest point of the exterior wall. 1. As this site is considered nonconforming for non-residential standards and you are proposing to add an additional rental unit to the site the site loses its nonconforming status and must be brought up to meet Unified Development Code (UDC) standards for vehicle & bicycle parking, landscaping, pedestrian circulation etc., see UDC Article 9.1. 2. A Development Package (DP) meeting the requirements of Administrative Manual 2-06 will need to be submitted and approved. This development package will need to demonstrate that the requirements of the UDC are met. The DP is a separate submittal from the building plans and is submitted at: https://docs.tucsonaz.gov/Forms/tucsonpermitapp, using the submission type “Site Review”. If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov. |
| 09/07/2021 | NOT AVAILABLE | ENGINEERING | REVIEW | Passed | PASSED BY SBLOOD 8/10/2021 |
| 09/08/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please provide electrical plans sealed by a Registrant registered in the State of Arizona... Revise reference for the 2018 IRC to 2017 NEC as this project is considered Commercial. Ref; 2018 IBC sec 107.1, 2917 NEC. |
| 09/08/2021 | JGARCIA1 | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. General: This is a commercial storage facility requesting a residential studio apartment to replace one of the storage units. This is considered a commercial project and must meet the criteria for a commercial review under the 2018 International Building Code. Per Section 107.1 of the IBC, all documents shall be prepared by a registered design professional as required by the City of Tucson. Please provide. |
| 09/08/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. General: This is a commercial storage facility requesting a residential studio apartment to replace one of the storage units. This is considered a commercial project and must meet the criteria for a commercial review under the 2018 International Building Code. Per Section 107.1 of the IBC, all documents shall be prepared by a registered design professional as required by the City of Tucson. Please provide. |
| 09/08/2021 | JGARCIA1 | WATER | REVIEW | Reqs Change | 1. General: This is a commercial storage facility requesting a residential studio apartment to replace one of the storage units. This is considered a commercial project and must meet the criteria for a commercial review under the 2018 International Building Code. Per Section 107.1 of the IBC, all documents shall be prepared by a registered design professional as required by the City of Tucson. Please provide. |
| 09/08/2021 | JGARCIA1 | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. General: This is a commercial storage facility requesting a residential studio apartment to replace one of the storage units. This is considered a commercial project and must meet the criteria for a commercial review under the 2018 International Building Code. Per Section 107.1 of the IBC, all documents shall be prepared by a registered design professional as required by the City of Tucson. Please provide. |
| 09/08/2021 | JGARCIA1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 09/13/2021 | JPEELDA1 | FIRE | REVIEW | Approved |