Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T21CM06459
Parcel: 13405119P

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM06459
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/19/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical review comments and provide a written response.
Per the response from Schnackel Engineering, the option for Electrical Energy conservation is ASHRAE 90.1.. Please show compliance on the electrical plans for section 8.4.2 (50% receptacle controls) and section 8.4.3 ( Electrical use energy measurement device installations). Or simply show compliance with section C405 2018 IECC for the lighting power conservation requirements in wattage allowed. As requested.
Ref 2018 IBC 107.2.1, 2017 NEC 2018 IECC.