Permit Number: T21CM06430
Parcel: 11703324A

Address:
721 N 3RD AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM06430
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/10/2022 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM06430
721 N 3rd Ave – HR-3
Studio/Carport (3rd Review)

TRANSMITTAL: January 10, 2022

COMMENTS: the following comments are relative to an application for Historic Review (UDC 5.8.8).

This site is located in the HR-3 zone (UDC 4.7.9). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.6.

The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure’s wall facing each interior property line (Table 6.3-2.A).

1. Based on a wall height of 9’-0” the required perimeter yard setback from the proposed Studio/Carport to the north property line is 6’-0” proposed setback is 3’-0”.

2. Based on a wall height of 9’-0” the required perimeter yard setback from the proposed Studio/Carport to the south property line is 6’-0” proposed setback is 1’-0”.

Historic review must be completed and approved prior to approval of this building permit. Historic review is a separate submittal from the building plan and is submitted at: https://www.tucsonaz.gov/pdsd-filedrop, using Submission Type “Historic Review”. Historic application/requirements can be found at: https://www.tucsonaz.gov/files/pdsd/Preservation/HPZ_Review_Application_Package_2020.pdf.

If you have any questions about this transmittal, please contact Elisa Hamblin at ElisaHamblin@tucsonaz.gov.
01/10/2022 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change Comply with Zoning requirements for placing the Carport within the setback.

Show the location of the Amvic wall on the Floor Plan.

Show the continuous Amvic foundation on the Foundation Plan.

Remove the Carport roof overhang on the Amvic Wall Detail.