Permit Number: T21CM06356
Parcel: 104090260

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM06356
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/09/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

Ref; Site Plan Sheet E2.1.

1 As requested per the previous plan review comments. (a) Show the location of the new and re- fed MH pedestals on the site plan. Include the relocated RV pedestals.

Ref; Line diagram Plan Sheet E 3.1.

1 As requested per the previous plan review comments. Provide a grounding detail for the New Service and grounding electrode systems at the MH pedestals per NEC 250 part 2, 250.32, 550.32.

(a) Provide 2 ground rods at each location requiring a grounding electrode, NEC 250.53.

(b) Provide a grounding electrode system at the relocated RV pedestals.

2 The conductor quantities shown in bold print for the 50- and 30-amp feeders do not correlate with the Proposed One Line Diagram. Please clarify.

3 Verify that the feeder conductor lengths between the 800-amp service and the 12x12 gutter do not exceed 2 feet. If they do, apply the conductor derating factors for the feeder conductors, per NEC 310.15(B)(3).

Ref; 2018 IBC sec 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements.