Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T21CM06356
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/09/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comments and provide a written response. Ref; Site Plan Sheet E2.1. 1 As requested per the previous plan review comments. (a) Show the location of the new and re- fed MH pedestals on the site plan. Include the relocated RV pedestals. Ref; Line diagram Plan Sheet E 3.1. 1 As requested per the previous plan review comments. Provide a grounding detail for the New Service and grounding electrode systems at the MH pedestals per NEC 250 part 2, 250.32, 550.32. (a) Provide 2 ground rods at each location requiring a grounding electrode, NEC 250.53. (b) Provide a grounding electrode system at the relocated RV pedestals. 2 The conductor quantities shown in bold print for the 50- and 30-amp feeders do not correlate with the Proposed One Line Diagram. Please clarify. 3 Verify that the feeder conductor lengths between the 800-amp service and the 12x12 gutter do not exceed 2 feet. If they do, apply the conductor derating factors for the feeder conductors, per NEC 310.15(B)(3). Ref; 2018 IBC sec 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. |