08/30/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical review comments and provide a written response.

Ref; Plan E3.1. Provide a grounding detail for the New Service and grounding electrode systems at the MH pedestals per NEC 250 part 2, 250.32, 550.32.

Show conduit, conductor sizes and types for the secondary conductors feeding the new service.

Show the location of the new and re- fed MH pedestals on the site plan.

Indicate whether the feeders are in conduit or direct burial. Indicate types of conduit, PVC etc.

Ref; 2018 IBC 107.2.1, 2017 NEC .