Permit Number: T21CM06353
Parcel: Unknown

Address:
3401 E GAS RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM06353
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/20/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change No attachment was found in the response that addressed compliance with IECC 2018. [Initial comment: Show that the proposed fan coils, chillers, cooling tower, water economizer, and boilers meet the requirements of Sections C403.3, C403.4, and C403.5 (e.g. provide the mechanical compliance certification from COMcheck). Reference: Section C501.4, International Energy Conservation Code 2018.]
09/20/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
09/30/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved