Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T21CM06353
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/20/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | No attachment was found in the response that addressed compliance with IECC 2018. [Initial comment: Show that the proposed fan coils, chillers, cooling tower, water economizer, and boilers meet the requirements of Sections C403.3, C403.4, and C403.5 (e.g. provide the mechanical compliance certification from COMcheck). Reference: Section C501.4, International Energy Conservation Code 2018.] |
09/20/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
09/30/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |