| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/19/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 08/24/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | A boxed note on sheet P301 states that the “NEW 14” GAS PIPING SIZED PER 2018 IFGC 402.4(2).” Table 402.4(2), IFGC 2018 requires a 2-inch pipe to deliver 2,000 CFH with a 0.5-inch water drop at 20-feet of developed length. Are you sure that you didn’t use Table 402.4(3), IFGC 2018? |
| 08/30/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical review comments and provide a written response. Ref; Plan Sheet E301. The Service Entrance Grounding Diagram has a note at the bottom referencing the Grounding Electrode System Conductor To be Sized per the line diagram... Where is the grounding conductor shown? Is the new SES rated the same as the existing one? Provide details. Ref; 2018 IBC 107.2.1, 2017 NEC . |
| 08/30/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Revise the configuration of the natural gas sediment trap, as shown in detail 1/M701, to comply with the requirements of Section 408.4, IFGC 2018 (i.e. the sediment trap is to be located downstream of the appliance shutoff valve, as close to the appliance as possible). 2. Show that the proposed fan coils, chillers, cooling tower, water economizer, and boilers meet the requirements of Sections C403.3, C403.4, and C403.5 (e.g. provide the mechanical compliance certification from COMcheck). Reference: Section C501.4, International Energy Conservation Code 2018. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/31/2021 | VVERA1 | OUT TO CUSTOMER | Completed |