Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T21CM06285
Parcel: 10606013D

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM06285
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/07/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical review comments and provide a written response.

The resubmitted plans did not satisfy the previous electrical plan review comments. Please see the comments. The revised plans (LINE DIAGRAM) did not include; 1. Conductor sizes and types for the secondary service conductors. 2. Load calculations were not included in the electrical plan. 3. Conduit sizes and types for the load feeders were not included in the electrical plan. 4. AIC rating of electrical equipment not included, verify with the supply utility for available fault current. 5. Is the new electrical service being installed in the same location as the old one? Please include this information on the electrical plans and re-submit.

Ref; 2018 IBC 107.2.1, 2017 NEC