| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/26/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical review comment and provide a written response. 1. The proposed work (per contractor) involves increasing the electrical service capacity up to 400 amps due tp a increase in load requirements. Please provide a complete electrical line diagram including load calculations and the entire scope of work, feeders etc , and if relocating the service ,provide a site plan showing the new location of the service on the premises. If not relocating the service, then specify this on the plan. Fer 2018 IBC 107.2.1, 2017 NEC. |