Permit Number: T21CM06284
Parcel: 10606013D

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T21CM06284
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/18/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. General: Please provide a site plan indicating the dimensional location of the new kiosk, with clearances from existing property lines, buildings, and other structures.
08/24/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
Provide plans and evidence on the plans that the proposed exterior lighting fully complies with the Outdoor Lighting Code. See section 104 for plan submittal requirements.
Provide lighting plans with the following information on the plans;
Provide a complete luminaire schedule.
Size of the parcel in acres.
See table 401.1, lighting area and option and indicate this information in the lighting site plan, also showing the locations and types of all exterior luminaires including existing.
(d) 402.1 (light source color temperature requirements), shielding requirements, etc .
(e) Provide calcs for total lumens allowed and total lumens proposed per acre including existing, for Full Cut Off and Unshielded per table 401.1.
(f) Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2.
(g) Specify any exceptions used.
(h) Curfew lighting controls If applicable.
Do not confuse the Outdoor Lighting Code with the IECC.
Ref; 2017 NEC, 2012 Tucson/Pima County Outdoor Lighting Code (OLC), 2018 IBC sec 107.2.1. 2018 IECC.
08/26/2021 SSHIELD1 ENGINEERING REVIEW Reqs Change See Zoning comments
08/26/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM06284
3910 N Flowing Wells Rd
Water & Ice Kiosk (1st Review)

TRANSMITTAL: August 26, 2021
This site is located in the C-1 zone (UDC 4.7.20). Food & Beverage Sales is a permitted use in this zone (Table 4.8-4). See Use Specific Standards 4.9.13.O.

1. Zoning has reviewed the building plans for compliance with DP21-0196 and although it appears that the building matches what is shown on the DP, until DP21-0196 is approved Zoning cannot approve the building plan.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/26/2021 NGARCIA3 OUT TO CUSTOMER Completed