Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T21CM06265
Parcel: 118036500

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T21CM06265
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/27/2022 PCAMARE1 OIP REVIEW Reqs Change Transmittal Template


FROM: Paul Camarena
PDSD Residential Review Section

PROJECT: T21CM06265
Roof top Solar Panels
2591 W BARBARY DR

TRANSMITTAL DATE: April 27, 2022



COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Residential Review Section comments were addressed.



COMMENT: Residential has reviewed the plan and cannot approve at this time. Please address the following comments


These comments are still applicable. Please provide a gas piping diagram, the flowing is required on the gas diagram: The total length of the pipe measured from the meter to the furthest appliance, The size and length of each pipe new and existing. The Btu/h input all gas-fired appliances supplied by the gas meter. Please use the link provided below for reference.
https://www.tucsonaz.gov/files/pdsd/permits/GAS_HANDOUT_2018_IRC_2019.2.4.pdf
CITY OF TUCSON Planning and Development Services
Updated 2019.2.4 Accessible shut-off valves shall be installed within 6 feet of the appliance ahead of the union connecting the appliance. Approved, and correctly sized flex connectors, shall be on site.
www.tucsonaz.gov
?



COMMENT: Provide the new gas pipe for the generator on the Gas piping template and show the new and existing gas pipes.

COMMENT: Residential will review the application on the next submittal



If you have any questions about this transmittal, Contact Paul Camarena any time during the week by email Paul.Camarena@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans

Final Status

Task End Date Reviewer's Name Type of Review Description
04/27/2022 NGARCIA3 OUT TO CUSTOMER Completed