Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T21CM06265
Parcel: 118036500

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T21CM06265
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/07/2022 PCAMARE1 OIP REVIEW Reqs Change FROM: Paul Camarena
PDSD Residential Review Section

PROJECT: T21CM06265
Roof top Solar Panels
2591 W BARBARY DR

TRANSMITTAL DATE: ?March ?7, ?2022


COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Residential Review Section comments were addressed.


COMMENT: Residential has reviewed the plan and cannot approve at this time. Please address the following comments


These comments are still applicable. Please provide a gas piping diagram, the flowing is required on the gas diagram: The total length of the pipe measured from the meter to the furthest appliance, The size and length of each pipe new and existing. The Btu/h input all gas-fired appliances supplied by the gas meter. Please use the link provided below for reference.
https://www.tucsonaz.gov/files/pdsd/permits/GAS_HANDOUT_2018_IRC_2019.2.4.pdf
CITY OF TUCSON Planning and Development Services
Updated 2019.2.4 Accessible shut-off valves shall be installed within 6 feet of the appliance ahead of the union connecting the appliance. Approved, and correctly sized flex connectors, shall be on site.
www.tucsonaz.gov
?



COMMENT: Provide the new gas pipe for the generator on the Gas piping template and show the new and existing gas pipes.

COMMENT: Residential will review the application on the next submittal


If you have any questions about this transmittal, Contact Paul Camarena any time during the week by email Paul.camarena@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans

Final Status

Task End Date Reviewer's Name Type of Review Description
03/07/2022 NGARCIA3 OUT TO CUSTOMER Completed