Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T21CM06258
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/05/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. 2. A lined water heater with a heat input in excess of 200,000 BTU per hour is considered a boiler and shall be installed in compliance with Section R20-5-404. (Standards for Boilers, Lined Hot Water Heaters and Pressure Vessels) of the Arizona Administrative Code. Reference: Article 4, Section R20-5-401, Arizona Administrative Code. http://apps.azsos.gov/public_services/Title_20/20-05.pdf 3. Plumbing fixtures that receive or discharge liquid waste (e.g. the mop sink) shall be directly connected to the sanitary drainage system. Reference: Section 301.3, IPC 2018. 4. Provide a detail of the water heater installation, including the excess pressure relief, expansion tank, vacuum relief or other anti-siphon device, safety pan, and valves. Reference: Sections 503.1, 504, 606.1, and 607.3, IPC 2018. 5. Provide a complete diagram of the natural gas distribution system showing the existing and proposed loads, developed lengths, and the new layout of the distribution piping. Reference: Section 402.2, IFGC 2018. |
| 08/26/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical review comments and provide a written response.!. Provide complete electrical plans to provide for the electrical requirements of the Boiler Unit. Ref; 2018 IBC 107.2.1, 2017 NEC |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/26/2021 | NGARCIA3 | OUT TO CUSTOMER | Completed |