Review Date Reviewer's Name Type of Review Description Status Comments
08/11/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.
STRUCTURAL REVIEW COMMENTS:
Denied
1. Provide a complete set a structural calculations for the new generator room.
BUILDING REVIEW COMMENTS:
Approved
ELECTRICAL REVIEW COMMENTS
Denied
E1.2 ELECTRICAL PLANS - 17TH FLOOR & ELEVATOR EQUIP RM: No electrical issues, Elevator conductor wire is oversized and may cause constructability issues.
E2.4 SYSTEMS PLANS - 17TH FLOOR: No electrical issues, Notes 1&2 not used?
E3.0 ONE LINE DIAGRAM AND CALCULATIONS:
1000 amp CB in MSB is undersized in relation to 1600 amp ATS and 600 KW generator. Panel load is below 1000 amps so this is not a code issue.
EM2 is 22KAIC rated on schedule and Fault current analysis calls for 42 KA rating. The short circuit calculation shows 23,485 Amps. Resolve.
Where is EMM panel?
Comment only: Transformer sizes seem non-standard.
E3.1 PANEL SCHEDULES:
Suggest to rephase ‘(Renamed EM4)’ to ‘(Formerly EM4)’
Confirm Existing EMP panel has several 1 Pole 60 amp Circuit breakers.
MECHANICAL REVIEW COMMENTS:
Approved Pending
1. Approved/subject to field approval
PLUMBING REVIEW COMMENTS:
N/A
08/19/2021 ROBERT SHERRY WATER REVIEW Completed
08/23/2021 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: T21CM06218
1501 N Oracle Rd
Elevator Modification and Site Work (1st Review)

TRANSMITTAL DATE: August 23, 2021

This site is located in the OCR-1 zone (UDC 4.7.26).

1. Per UDC Article 3.3.3.G.2.c A site plan is required for the following types of development: c. Existing development undergoing a change of use , building or structure additions, and/or a reconfiguration of an area outside a building. That said as you are proposing a reconfiguration of an area outside a building a Development Package (DP)meeting the minimum requirements of the checklist for Minor Changes to Commercial/Industrial Sites found at: https://www.tucsonaz.gov/files/pdsd/forms/Minor_Changes_to_Commercial_Industrial_Sites_.pdf, must be submitted and approved showing how the pedestrian circulation will be provided. Only minor changes such as upgrades to accessible vehicle parking and accessible access are allowed on tenant improvement plans. If you elect to eliminate a required pedestrian circulation component A Board of Adjustment for Variance will be required.

The DP is a separate submittal from the building plans and is submitted at: https://docs.tucsonaz.gov/Forms/tucsonpermitapp, using Submission Type “Site Review”.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin @tucsonaz.gov or (520) 837-4966
08/30/2021 SBLOOD1 ENGINEERING REVIEW Reqs Change See Zoning comment about need for a DP
08/30/2021 JPEELDA1 FIRE REVIEW Approved
10/07/2021 DBENOIT1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Reqs Change