Review Details: COMMERCIAL - TI

Permit Number - T21CM06186
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/17/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Appliances (e.g. beverage dispensers, etc.) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Section 608.14.1, IPC 2018 require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 608.1 and 608.3, IPC 2018.
2. Verify that the hand sinks and the new floor sink discharge through a grease interceptor. Hand sinks are allowed to connect to the sanitary waste system instead of the grease waste system only if each sink has a sign posted above it stating, “HANDWASH SINK ONLY! NO FOOD PREPARATION OR DISHWASHING ALLOWED.” Reference: Section 1003.3, IPC 2018, as amended by the City of Tucson.
08/17/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
08/24/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved