Permit Number - T21CM06181
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/25/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The inside diameter of PEX is significantly smaller than galvanized carbon steel pipe. To maintain the maximum water velocity at 8 feet per second or less, the cold water main will need to be increased to 2-inches and the cold water drops to each apartment will need to be increased to 1-inch.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/26/2021 NGARCIA3 OUT TO CUSTOMER Completed