Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T21CM06165
Parcel: 116206300

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM06165
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/04/2021 JPEELDA1 FIRE REVIEW Approved
08/09/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
08/10/2021 SBLOOD1 ENGINEERING REVIEW Passed
08/12/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Drawing G0.0 shows a single drinking fountain located outside of the restrooms. Section 410.3, IPC 2018 clearly states that a minimum of two drinking fountains are required, one for people that use a wheelchair and one for standing persons. Alternatively, a drinking fountain with two spouts (one high and one low) is acceptable
08/12/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
08/12/2021 ROBERT SHERRY WATER REVIEW Completed
08/23/2021 STEVE SHIELDS ZONING REVIEW Approved
08/23/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
08/24/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved