Permit Number: T21CM06160
Parcel: 11205055C

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM06160
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/04/2021 JPEELDA1 FIRE REVIEW Approved
08/09/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A1; New Floor Plan: There are two separate suite numbers for this building. However, there is interior access from one office to the other. Two separate Certificate of Occupancies will be required since the area and occupant load of each is changing. Please verify.
2. Sheet A1; New Floor Plan: There are several locations where a 6B Partition Type is indicated (one hour fire resistance rating). Is a fire rated wall required at these locations? There is no indication on this plan that any interior partitions are fire resistance rated. Please verify.
3. Sheet A1; New Floor Plan: The main exit doors for the two separate offices so not meet the separation requirements per the IBC Section 1007.1.1. Please verify.
4. Sheet A1; New Floor Plan: Is the intent of the new fire resistant rated wall to separate the common corridor area from the Leoni office side? All existing walls in that area must also meet the required fire resistance rating in order to separate the two offices. Please verify.
5. Sheet A3; Enlarged Floor Plan: Please indicate on a bathroom elevation the location of the shower control and handshower per the ICC/ANSI Section 608.4.
6. General: Please provide written responses to all review comments.
08/12/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. The architect has installed a fire-rated partition (6B) on the north and west sides of the new common corridor as well as the south side of room 301. It is not clear if any other partitions are fire-rated. Coordinate the duct penetrations with the architect. Reference: Section 607.1.2, IMC 2018.
2. Specify the exhaust air flowrate for the new restroom/shower room. Describe how the exhaust fans will be controlled. Reference: Section 403.3.1.1, IMC 2018.
08/12/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
08/12/2021 ROBERT SHERRY WATER REVIEW Completed
08/23/2021 STEVE SHIELDS ZONING REVIEW Approved
08/23/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
08/23/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/30/2021 SBLOOD1 ENGINEERING REVIEW Reqs Change This project is within a mapped flood hazard area and requires a Floodplain Use Permit (FUP.)
Please start a new FUP at our permit application web page: https://docs.tucsonaz.gov/Forms/tucsonpermitapp.
Instructions:
1. Is this for a new or existing activity application? - Please select New Application.

2. Submission Type - Select Floodplain Use Permit.

3. Project Name - Enter a name for your project.

4. Select Street Name from the list. You can type the first two letters or number to get closer to your choice in the list. Then select the rest of the address in the boxes provided.

5. Type of Permit - Select Commercial or Residential (Residential is for work on single family residences and duplexes.)

6. Complete the Applicant Info. (Note APA# is for applicants with an advance payment account. Leave blank is you do not have an APA account.

7. Complete the Contractor, Owner and Architect/Engineer sections as applicable.

8. Supporting Documentation Upload - Provide a complete cost estimate for the project. You may also provide additional documents you think will be helpful.

9. Sign the application and submit.


Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov