Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T21CM06110
Parcel: Unknown

Review Status: Completed

Review Details: OTHER

Permit Number - T21CM06110
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/23/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A1; Code Review: Please include the plumbing fixture requirements in the Code Review per the IBC Table 2902.1.
2. Sheet A2; Floor Plan: Per the IEBC Section 305.8.10, an accessible restroom is required where there is a change of occupancy in the tenant space. This can be accomplished by altering the existing restroom, or adding a unisex restroom. Please verify and revise as required. Indicate a change in the project valuation for this issue.
3. Sheet A2; Floor Plan: Per the IBC Section 1016.2(3), exit access shall not pass through a room that can be locked to prevent egress. Please indicate on the plan the new door in the new interior partition meets that requirement.
4. Sheet A2; Floor Plan: Per the IBC Section 1016.2(5)(2), egress for an M occupancy classification is not prohibited through stockrooms if certain requirements are met. Please indicate on the plan those requirements.
5. General: Please provide written responses to all review comments.
08/24/2021 STEVE SHIELDS ZONING REVIEW Approved
08/26/2021 JVINCEN1 FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/26/2021 NGARCIA3 OUT TO CUSTOMER Completed