Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T21CM06108
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/11/2021 | PCAMARE1 | OIP | REVIEW | Reqs Change | FROM: Paul Camarena PDSD Residential Review Section PROJECT: T21CM06108 Roof top Solar Panels (1st Review) 220 W LINCOLN ST TRANSMITTAL DATE: August 11, 2021 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Residential Review Section comments were addressed. COMMENT: Residential has reviewed the plan and cannot approve at this time. Please address the following comments. COMMENT: This plan set is not compliant with the Fire code, demonstration compliance to 2018 International Fire Code 1204.2.1.1. If the slope of the building is greater than 2:12 then compliance must be shown on the plans. Show a 36” wide access pathway from the eave to the ridge on both sides of the building. MP2 and MP3 have a roof slope of 30 degrees COMMENT: Residential will review the application on the next submittal If you have any questions about this transmittal, Contact Paul Camarena any time during the week by email Paul.camarena@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/11/2021 | VVERA1 | OUT TO CUSTOMER | Completed |