Permit Number: T21CM06104
Parcel: 136131840

Address:
8842 E ARBOR ST

Review Status: Completed

Review Details: OTHER

Permit Number - T21CM06104
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/11/2021 KKARSEN1 OIP REVIEW Reqs Change T21CM06104
PLAN REVIEW COMMENTS
Plan review for the above referenced structure is completed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code, 2018 International Fire Code, 2017 National Electrical Code and Arizona Revised Statutes. All features were checked to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

1. Show the sum of the main and backfeed breakers not exceeding 120% of the busbar (and conductor) rating, NEC 690.64 & 705.12 (D). The distribution panel bus and extended bus conductor (4) requires a rating for receiving electrical power from two sources. Show the backfeed breaker incompliance with the bus limitation or increase the service panel rating.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
08/11/2021 VVERA1 OUT TO CUSTOMER Completed