Permit Number: T21CM06081
Parcel: 13315320E

Address:
2130 N KOLB RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM06081
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/04/2021 JPEELDA1 FIRE REVIEW Approved
08/07/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
08/10/2021 ROBERT SHERRY WATER REVIEW Completed
08/10/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
08/11/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Footnote b on Table 403.3.1.1, IMC 2018 states that mechanical exhaust is required for the kitchen and no air from the kitchen may be recirculated to any other space. HP-1 and HP-2 appear to be recirculating air from the kitchen/prep, the order line, and to the public restroom. Reference: Section 403.2.1 (3), IMC 2018.
08/18/2021 STEVE SHIELDS ZONING REVIEW Approved
08/18/2021 SSHIELD1 ENGINEERING REVIEW Passed
08/18/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide a written response to the review comment.
#1. Ref; Plan Sheet E1.1. The power plan shows 2 - 'A' panels, 1 existing and 1 new. Please clarify and resubmit. #2. Provide compliance with the 2012 Tucson/Pima County Outdoor Lighting Code for the Exterior lighting. See section 104 for Plan Submittal Requirements.
Code Ref; 2018 IBC 107.2.1, 2017 NEC. 2012 Tucson/Pima County Outdoor Lighting Code
08/18/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed