Permit Number - T21CM06081
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/04/2021 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 08/07/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 08/10/2021 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 08/10/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 08/11/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Footnote b on Table 403.3.1.1, IMC 2018 states that mechanical exhaust is required for the kitchen and no air from the kitchen may be recirculated to any other space. HP-1 and HP-2 appear to be recirculating air from the kitchen/prep, the order line, and to the public restroom. Reference: Section 403.2.1 (3), IMC 2018. |
| 08/18/2021 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 08/18/2021 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
| 08/18/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please provide a written response to the review comment. #1. Ref; Plan Sheet E1.1. The power plan shows 2 - 'A' panels, 1 existing and 1 new. Please clarify and resubmit. #2. Provide compliance with the 2012 Tucson/Pima County Outdoor Lighting Code for the Exterior lighting. See section 104 for Plan Submittal Requirements. Code Ref; 2018 IBC 107.2.1, 2017 NEC. 2012 Tucson/Pima County Outdoor Lighting Code |
| 08/18/2021 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |