Permit Number: T21CM06049
Parcel: 10824086A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM06049
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/03/2021 JPEELDA1 FIRE REVIEW Approved
08/04/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
08/10/2021 ROBERT SHERRY WATER REVIEW Completed
08/10/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
08/10/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
08/17/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments and provide a written response.

Provide full compliance with the 2018 IECC for the lighting.

Verify Requirements are met for receptacles required, branch circuits, per NEC art 517.19C.

Provide a note on the power/lighting plan branch circuit wiring methods to comply with NEC art 517.13

Is panel ISO-C2 new or existing? If new, indicate this on the plan.

Ref; 2018 IBC sec. 107.2.1, 2018 NEC, City of Tucson Commercial Plan Submittal Requirements.
08/18/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/18/2021 SSHIELD1 ENGINEERING REVIEW Passed
08/18/2021 STEVE SHIELDS ZONING REVIEW Approved