Permit Number: T21CM06048
Parcel: 112040640

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T21CM06048
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/09/2021 LSHAMIS1 ZONING REVIEW Reqs Change CDRC Transmittal

FROM: Loran Shamis
PDSD Zoning Review Section

PROJECT: T21CM06048
SFR - addition and casita remodel (1st Review)
2551 E Monte Vista Rd

TRANSMITTAL DATE: August 9, 2021

DUE DATE: August 9, 2021

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

The proposed use is two (2) unit single family residential, which is permitted in the R-1 zone (minimum 10,000 sf lot size required), with use-specific standards 4.9.7.B.1 - .9, .11 applicable (UDC, Table 4.8-2).

01. COMMENT: Provide a site plan with the following information - https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf

02. COMMENT: Provide the setback dimensions, both required and proposed. The required setbacks for the north, east and west parcel boundaries are 6' or 2/3 the height of the adjacent wall, measured from the property line to the exterior wall of the adjacent structure, the greater will apply. The required setback for the south parcel boundary is 25' per the subdivision plat (M&P, Book 7, Page 92).

03. COMMENT: It appears the casita is not meeting setback requirements. If this is the case, a neighbor waiver sign-off will be required to reduce the setback requirements. Copy the following language onto the site plan with the adjacent neighbors' signatures in the direction where the setbacks are not being met (2550 E La Madera Dr. and 2543 E Monte Vista Dr.)

"My Name is ________________ and I am the owner of the property located at ___________. I have reviewed the site plan and I have no objection to the structure being located or constructed ______ feet from the property line as depicted on the site plan."

04. COMMENT: The gross size of the lot is incorrect. Based on the subdivision map plat and the dimensions provided in this plan, the size of the parcel is 10,125 square feet or 0.23 acres, please correct this on the plans.

05. COMMENT: Provide a lot coverage calculation including all buildings, storage areas, and vehicular use area as a percentage of the total site.

06. COMMENT: Provide building elevations of the additions and the casita to determine setback requirements. The setback is based on the maximum height of the adjacent wall measured from grade.

07. COMMENT: Indicate all existing or proposed easements - there is a 5' utility easement along the northern parcel boundary per the subdivision plan (M&P, Book 7, Page 92).

08. COMMENT: Please submit the plans as one document for the next submittal.

For questions regarding Zoning comments, please contact me at: Loran.Shamis@tucsonaz.gov
To resubmit your plans for additional review, please visit: https://docs.tucsonaz.gov/Forms/tucsonpermitapp
08/18/2021 AWARNER1 NPPO REVIEW Passed
08/23/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T21CM06048
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide an updated complete plan set with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

The City of Tucson adopted the 2018 IRC with amendments on 1/1/2019. Show the current code reference on the plans.

Consolidate pages of construction plans into a single .PDF file as prescribed at the PDSD web site.

A dwelling unit (casita with a kitchen) requires a separate permit. The casita will be considered a detached sleeping quarters rather than a dwelling unit if the cooking range and electrical circuit is removed.

A dwelling unit (includes a kitchen) requires collection of development impact fee when the building permit is processed, City of Tucson Ordinance #11203.

Each dwelling unit building requires a separate Pima County assigned street address, R319. Notate each dwelling address on the site plan. A separate building permit is required for each dwelling unit.

SITE PLAN:

1. Indicate the location and size of buildings, utility meters and gas, water, electric and sewer or septic lines from property line to building, R106.1.1. Show the utility lines requiring upgrade or replacement.

FLOOR PLANS:

1. Show the casita bedroom window size for determining compliance with R310 providing egress from bedrooms. Requires a minimum net clear opening area of 5.7 SQ FT (5 SQ FT 1st floor). Also, show the minimum net clear opening dimension of 24” height and 20” width, and maximum sill height of 44”.

STRUCTURAL PLANS:

1. Provide manufacturer’s calculations and data for pre-engineered trusses dated and wet-sealed by an engineer who is registered in Arizona, or notate the requirement for deferred submittal, R106.1.
2. Provide a complete roof framing plan with beams and rafters sized with appropriate load carrying capacity, R301.1.
3. Provide a header schedule and show opening sizes supporting new roof consistent with Table 502.5(1) & R602.7(1).

SECTIONS - DETAILS:

1. Clarify the placement of ceiling/roof insulation for determining the need for attic ventilation, R806. The space between roof insulation and ceiling may not be vented.
2. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38 or R-30 when extended over the wall top plate for additions under 500 SF.
3. A vented attic space requires a calculation for showing the attic ventilation opening size using 1 to 150 of attic area in compliance with R806.2. Provide appropriate upper and lower space vents when applying the reduced area calculation. Account for the existing attic space if removing or blocking existing vents. Show the insulation at the ceiling level if providing a vented attic space.

PLUMBING PLANS:

1. Clarify the casita drain and vent pipe sizes and locations.
2. Show an individual accessible water supply shut off for each dwelling unit, P2903.9.1.
3. Provide the water pipe diameter between the meter and shut off valve in compliance with P2903.7. A minimum 1” service pipe is required for supplying water to more than 9.5 fixture units.
4. Provide branch drainpipes in accordance with Table P3005.4.1. The minimum water closet pipe diameter is 3”.

MECHANICAL PLANS:

1. Provide heating facilities in all habitable rooms, R303.9. Show the size and location on the casita plan.

ELECTRICAL PLANS:

1. TEP usually requires the service panel on the property at the closest building to the service transformer. The overhead service conductor over the proposed building requires an 8’ clearance above the roof, E3604.2.1. The necessary mast height at the existing panel location is not a feasible installation.
2. Provide an Electrical service utility plan coordinated with Tucson Electric Power. Two dwelling units (casita with range) or one dwelling with detached sleeping quarters (casita without range).
3. Clarify if the electrical service panel is existing or replaced on the riser diagram. Include a service for each dwelling or a service and sub panel if the casita is a sleeping quarters. E3403
4. Provide separation of all circuits for each building and update the circuit designations, E3601.3.
5. Show two or more 2O AMP small appliance circuits at the kitchen countertop receptacle outlets; they may also serve the breakfast room and dining room, but not other locations, E3703.2 and E3901.3. GFCI protected, E3902.6.
6. Show one 20 AMP branch circuit in the laundry area; this circuit may not serve other locations, E3703.3 and 3901.8.
7. Show one 20 AMP branch circuit for the dishwasher/disposal; this circuit may not serve other locations, E3703.8 City of Tucson Amended.
8. Show at least one wall switch controlled light at outdoor entrances or exits, E3903.3.
9. Provide an exterior outlet at grade level located at both the front and back of the dwelling, E3901.7. These outlets require GFCI protection, E3902.3.
10. Clothes Washer and Dishwasher GFCI: receptacles require readily accessible protection typically from an upstream device, E3902.9 & 10. Add notation to plans.
11. Show or notate a disconnect means or a locking breaker for the water heater, E4101.5.
12. Smoke alarms are required outside each separate sleeping area, R314.3.2. Show a smoke alarm in each bedroom and outside in the immediate vicinity.

OUTDOOR LIGHTING CODE

1. Show the proposed fixture as full cut-off FCO style or provide an Outdoor Lighting Calculation including all exterior fixtures on the property for determining exterior lighting limits. Adjustable security light fixtures are unshielded, not FCO.

If you have any questions, please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review
09/08/2021 SBLOOD1 ENGINEERING REVIEW Reqs Change 1. Until Floodplain Use Permit is issued engineering can't approve the building permit.
Outstanding issue on FUP:

This project site is mapped within a city of Tucson Estimated Flood Hazard Zone.
As per city code for a substantial improvement if a project site is within the floodplain - the sum of all improvements within any ten year period is limited to 50% of the value of the structure or the structure must be improved to floodplain standards (or verified that it is up to floodplain standards). According to pima county assessor's records the market value of the existing house is $ 152,750 (65% of most recent sale value of $235,000). That puts the proposed work of $90,000 at 58.9% which is over the 50% and therefore is classified as a substantial improvement. So you can either reduce the scope of the project, provide a higher appraisal of the house, or bring the house and proposed work to floodplain standards.
If you have any questions don't hesitate to reach out to me.

Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov