Permit Number: T21CM06026
Parcel: 11451216G

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM06026
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/27/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Comment not addressed. (See also General Note #1 on sheet P1) [Initial comment: This project is under the jurisdiction of the City of Tucson, not Phoenix (General Note #1).]
2. Comment not addressed. [Initial comment: Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restroom will be exhausted (i.e. all of the air supplied to each restroom is to be exhausted during the hours of operation even if the lights are off). Reference: Section 403.2.1 (4), IMC 2018.]
09/27/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Comment not resolved - note not found. [Initial comment: Specify that all proposed plumbing fixtures shall be listed by a third-party certification agency as complying with the relevant standards. Reference: Section 303.4, IPC 2018.]
2. Comment not addressed. [Initial comment: The replacement faucet for the lavatory shall be a metering faucet. The metering faucet shall dispense a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10-seconds for accessibility. Reference: Section 412.11, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.]
10/11/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Previous electrical review comments not addressed.
A written comment response for electrical was not found in the 2nd submittal. No compliance with the 2018 IECC for the lighting.
2018 IBC 107.2.1. 2017NEC, 2018 IECC.