Permit Number: T21CM06026
Parcel: 11451216G

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM06026
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/26/2021 SBLOOD1 ENGINEERING REVIEW Passed
08/03/2021 JPEELDA1 FIRE REVIEW Approved
08/04/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
08/10/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. This project is under the jurisdiction of the City of Tucson, not Phoenix (General Note #1).
2. Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restroom will be exhausted (i.e. all of the air supplied to each restroom is to be exhausted during the hours of operation even if the lights are off). Reference: Section 403.2.1 (4), IMC 2018.
08/10/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Specify that all proposed plumbing fixtures shall be listed by a third-party certification agency as complying with the relevant standards. Reference: Section 303.4, IPC 2018.
2. The replacement faucet for the lavatory shall be a metering faucet. The metering faucet shall dispense a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10-seconds for accessibility. Reference: Section 412.11, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
08/10/2021 ROBERT SHERRY WATER REVIEW Completed
08/17/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Provide complete compliance with the 2018 IECC for the lighting.
08/18/2021 STEVE SHIELDS ZONING REVIEW Approved
08/18/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed