Permit Number: T21CM06013
Parcel: 110094370

Review Status: Completed

Review Details: OTHER

Permit Number - T21CM06013
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/26/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Clarify the drawing. Provide a complete diagram of the natural gas distribution system showing all of the loads, developed lengths, and the layout of the distribution piping. Show the location of the gas meter on the drawing. Provide a north arrow. Reference: Section 402.2, IFGC 2018.

Final Status

Task End Date Reviewer's Name Type of Review Description
07/27/2021 NGARCIA3 OUT TO CUSTOMER Completed