Review Date Reviewer's Name Type of Review Description Status Comments
07/23/2021 SBLOOD1 ENGINEERING REVIEW Passed
08/10/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM06000
2202 E 3rd St – R-1
Master Suite & Family Room Addition and Detached Garage (1st Review)

TRANSMITTAL: August 10, 2021
COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1).

This site is located in the R-1 zone (UDC 4.7.1). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9. 10.

The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure’s wall facing each interior property line (Table 6.3-2.A).
1. Based on a wall height of 12’-0” the required perimeter yard setback from the proposed detached garage to the south property line is 8’-0”, proposed setback is 2’-0”.

The minimum setback to a side street property line is ten (10) feet (UDC Section 6.4.5.C.1.b).
2. Setback proposed from the Master Suite addition to the side street, Plumer Av. property line is 8’-0”.
3. As a side street perimeter yard setback was not provided from the detached garage to the Plumer Av. property line side street perimeter yard requirements cannot be verified.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov
08/18/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change Requires Design Development Option approval before construction plan submittal.