Permit Number: T21CM05975
Parcel: 13325183D

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T21CM05975
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/09/2021 JPEELDA1 FIRE REVIEW Reqs Change Need more information. Ramada appears to be in the parking lot of a strip mall. Maybe attached to a restaurant in the parking lot. Please provide more detailed information as to location and use.

Questions:
Jennifer.Peel-Davis@Tucsonaz.gov
520-837-7033
08/12/2021 NMARTEL1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Reqs Change
08/12/2021 NMARTEL1 ZONING REVIEW Reqs Change PDSD TRANSMITTAL
Nicholas Martell, Planner
T21CM05975
Ramada on Commercial Property
August 12, 2021

The plans have been reviewed by the Zoning Review Section but zoning cannot determine the scope of work. If the applicant is proposing to build a ramada at 8550 E Broadway, a development package will be necessary to go forward with the project. The development package is the application required for any change to the footprint of a commercial site. It appears that the proposal is to add a ramada to a shopping center.

The development package must follow section 2-06 of the city of Tucson Administrative Manual. Parking calculations, pedestrian ciculation, access, setbacks, and other standards must be provided.

The application for the development package can be found here: https://www.tucsonaz.gov/files/pdsd/forms/Development_Package_and_Land_Division-Subdivision_Application.pdf

Please refer to the following checklist of requirements to submit a development package: https://www.tucsonaz.gov/files/pdsd/forms/Submittal_Requirements.pdf

If you have any questions, please contact me at Nicholas.Martell@tucsonaz.gov

Please Submit: Development Package
08/12/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. General: Please provide a site plan. Dimensionally locate the ramada from existing buildings, structures, and property lines.
2. General: Please provide a Code Analysis for this structure, including applicable codes, occupancy classification, construction type, and SF. This could be included on the new site plan sheet.
3. General: Please provide the material strengths for the new ramada and its foundation. This could be included on the new site plan sheet.
4. General: Please provide structural calculations for the ramada framing and its foundation.
5. General: Please provide written responses to all review comments.
09/08/2021 SBLOOD1 ENGINEERING REVIEW Reqs Change Please include a site plan that clearly identifies the scope of work in the next submittal.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/08/2021 NGARCIA3 OUT TO CUSTOMER Completed