Review Date Reviewer's Name Type of Review Description Status Comments
07/26/2021 SBLOOD1 ENGINEERING REVIEW Passed
08/03/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
08/03/2021 JPEELDA1 FIRE REVIEW Approved
08/05/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
08/05/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Show how the dryer installation complies with Section 504.6, IMC 2018.
08/05/2021 ROBERT SHERRY WATER REVIEW Passed
08/16/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments and provide a written response.

Revise references to 2011 NEC and IRC to 2017 NEC.

Indicate raceway, sizes and type of the new panel feeder and show the location of the new panel in the electrical floorplan.

Provide Gfi and arcfault protection the the washer circuit. NEC 210.8, 210.12.

Ref; 2018 IBC sec. 107.2.1, 2018 NEC, City of Tucson Commercial Plan Submittal Requirements.
08/17/2021 STEVE SHIELDS ZONING REVIEW Approved
08/17/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed