Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T21CM05974
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/26/2021 | SBLOOD1 | ENGINEERING | REVIEW | Passed | |
| 08/03/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 08/03/2021 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 08/05/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 08/05/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Show how the dryer installation complies with Section 504.6, IMC 2018. |
| 08/05/2021 | ROBERT SHERRY | WATER | REVIEW | Passed | |
| 08/16/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments and provide a written response. Revise references to 2011 NEC and IRC to 2017 NEC. Indicate raceway, sizes and type of the new panel feeder and show the location of the new panel in the electrical floorplan. Provide Gfi and arcfault protection the the washer circuit. NEC 210.8, 210.12. Ref; 2018 IBC sec. 107.2.1, 2018 NEC, City of Tucson Commercial Plan Submittal Requirements. |
| 08/17/2021 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 08/17/2021 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |