Permit Number: T21CM05947
Parcel: 13604814A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM05947
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/29/2021 JVINCEN1 FIRE REVIEW Approved
08/02/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A-101; North Bathroom Elevation: Please indicate on this sheet the dimensional location of the side wall horizontal grab bar from the back wall per the ICC/ANSI Figure 604.5.1.
2. Sheet A-101; West Bathroom Elevation: Please indicate on this sheet the dimensional location of the back wall horizontal grab bar from the centerline of the water closet per the ICC/ANSI Figure 604.5.2.
3. Sheet A-101; Bathroom Elevations: Please indicate on this sheet the dimensional locations of the grab bars in the roll-in-type shower per the ICC/ANSI Section 609.
4. Sheet A-101; Bathroom Elevations: Please indicate on this sheet the dimensional locations of the roll-in-type shower control and hand shower per the ICC/ANSI Section 608.4.
5. Sheet A-101; Bathroom Elevations: Please indicate on this sheet the requirements of the ICC/ANSI Section 610 for the roll-in-type shower seats.
6. General: Please provide written responses to all review comments.
08/02/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
08/02/2021 ROBERT SHERRY WATER REVIEW Completed
08/03/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Verify that the pipe sizes called out for the flush valves will not result in water velocities greater than that recommended by the pipe manufacturer (e.g. limit the water velocity to less than 8 FPS for copper piping). At a minimum design flow rate of 25 GPM for a siphonic, flush-valve water closet, a 1” Type L copper pipe has a flow velocity of 9.7 FPS and a ¾” Type L copper pipe has a flow velocity of 16.6 FPS. Reference: Table 604.3, IPC 2018.
2. Revise the hot water supply to the new lavatory, P-1, so that the distance from the hot water source to the hot water termination for P-1 complies with the requirements of Section C404.5, IECC 2018 (i.e. 24-inches for ½-inch pipe).
3. Fixtures other than floor drains, sinks, lavatories, and drinking fountains, are not permitted to be included in a combination waste and vent system. Reference: Section 915.1, IPC 2018.
4. Coordinate the waste and water isometric (4/P-101) with the plumbing floor plan (2/P-101). The isometric shows P-3 with an individual vent.
08/12/2021 NMARTEL1 ZONING REVIEW Approved
08/12/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
08/12/2021 NMARTEL1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/24/2021 LOREN MAKUS ENGINEERING REVIEW Passed FUP not required. Black Rock Coffee drainage report shows floodplain not in effect.