Permit Number: T21CM05941
Parcel: 129053010

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T21CM05941
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/23/2021 SBLOOD1 ENGINEERING REVIEW Passed
08/06/2021 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: T21CM05941
2307 E Eastland ST – R-1
Porch Addition (1st Review)

TRANSMITTAL DATE: July 21, 2021

This site is located in the R-1 zone (UDC 4.7.8). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9.

1. Provide a plot plan that meets the requirements found at: https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf. All information shall be provided.

2. For your information the street property line is located 12’ from the face of curb along Eastland. Face of curb is where street pavement meets the concreate curb. The street perimeter yard is measured from the street property and the required setback is 20’-0”


If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov
08/17/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change A structural engineer may provide an analysis and sealed plans for structures not built with 2018 IRC minimum requirements.

Show rafters placed on top of a manufacturered appropriate (actually available) GLB size with H2.5 type uplift rated fasteners.

Limit cantilevered rafters (overhang) to 24”, R802.7.1.1.

A special inspection request is required with the permit application for welding, R109.2.