Permit Number: T21CM05936
Parcel: 11507236A

Address:
1550 N ORACLE RD

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T21CM05936
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/02/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM05936

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
Approved

BUILDING REVIEW COMMENTS:
Denied
1. The doors in new corridor created by the new addition now encroach into the path of egress. Provide doors or corridor widths that comply with Section 1005.7.1
2. Floor plan keynote 11 indicated on the plans. No plan note provided.
3. The reroute of down spout may cause headroom issues. Comply with Section 103.3.1
4. Provide an updated egress plan showing distances.

MECHANICAL REVIEW COMMENTS:
Approved

ELECTRICAL REVIEW COMMENTS
Approved

PLUMBING REVIEW COMMENTS:
NA
08/12/2021 ROBERT SHERRY WATER REVIEW Completed
08/16/2021 STEVE SHIELDS ZONING REVIEW Approved
08/16/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
08/20/2021 JVINCEN1 FIRE REVIEW Approved
09/01/2021 SBLOOD1 ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
09/02/2021 VVERA1 OUT TO CUSTOMER Completed