Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T21CM05935
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/02/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
09/02/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
09/13/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments and provide a written response, The exhaust fans, water heater and disconnecting means, recirculation pump, are not located on the electrical floor plans. Please correlate the exhaust fans and recirculation pump with the panel schedule as applicable. As requested per the previous electrical plan review. REF; 2018 IBC 107.2.1, 2017 NEC, |