Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T21CM05935
Parcel: Unknown

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM05935
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/02/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
09/02/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
09/13/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments and provide a written response,

The exhaust fans, water heater and disconnecting means, recirculation pump, are not located on the electrical floor plans. Please correlate the exhaust fans and recirculation pump with the panel schedule as applicable. As requested per the previous electrical plan review.

REF; 2018 IBC 107.2.1, 2017 NEC,