Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T21CM05935
Parcel: Unknown

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM05935
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/29/2021 JVINCEN1 FIRE REVIEW Approved
08/02/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
08/02/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change This tenant improvement has added 375 CFM of exhaust to the suite. Verify that the suite has sufficient outside air to maintain an essentially neutral air pressure. Reference: Section 403.1, IMC 2018.
08/02/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The distance from the hot water source to the hot water termination for the public lavatories does not appear to comply with the requirements of Section C404.5, IECC 2018
08/02/2021 ROBERT SHERRY WATER REVIEW Completed
08/11/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments and provide a written response.

Please coordinate with Mechanical and Plumbing, revise the plans to correctly and clearly indicate the scope of work. Show electrical for the Mechanical/Plumbing equipment on the electrical plans.

Provide complete panel schedules, Including new loads.

Provide compliance with the 2018 IECC for the lighting.

Ref; 2018 IBC sec. 107.2.1, 2018 NEC, City of Tucson Commercial Plan Submittal Requirements.
08/16/2021 SSHIELD1 ENGINEERING REVIEW Passed
08/16/2021 STEVE SHIELDS ZONING REVIEW Approved
08/16/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed