Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T21CM05935
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/29/2021 | JVINCEN1 | FIRE | REVIEW | Approved | |
| 08/02/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 08/02/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | This tenant improvement has added 375 CFM of exhaust to the suite. Verify that the suite has sufficient outside air to maintain an essentially neutral air pressure. Reference: Section 403.1, IMC 2018. |
| 08/02/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | The distance from the hot water source to the hot water termination for the public lavatories does not appear to comply with the requirements of Section C404.5, IECC 2018 |
| 08/02/2021 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 08/11/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments and provide a written response. Please coordinate with Mechanical and Plumbing, revise the plans to correctly and clearly indicate the scope of work. Show electrical for the Mechanical/Plumbing equipment on the electrical plans. Provide complete panel schedules, Including new loads. Provide compliance with the 2018 IECC for the lighting. Ref; 2018 IBC sec. 107.2.1, 2018 NEC, City of Tucson Commercial Plan Submittal Requirements. |
| 08/16/2021 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
| 08/16/2021 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 08/16/2021 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |