Permit Number: T21CM05931
Parcel: Unknown

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM05931
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/29/2021 JVINCEN1 FIRE REVIEW Approved
08/02/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A2.0; Wall Types: Wall Type C indicates a new partial height wall up to 3'-4" top of counter. Per the ICC/ANSI Section 904, the service counter surface shall be a maximum of 36" above the floor. Please verify.
08/02/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
08/02/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
08/02/2021 ROBERT SHERRY WATER REVIEW Completed
08/05/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments and provide a written response.

1. Provide complete compliance with the 2018 IECC for the lighting, Including controls (switching).

2. Verify receptacle placement and quantity in the conference room as required per NEC art 210.71.

3. Provide a complete panel schedule including load calculations. The General Notes for the lighting did not indicate. Also identify the panel on the panel schedule.

Ref; 2018 IBC sec. 107.2.1, 2018 NEC, City of Tucson Commercial Plan Submittal Requirements.
08/16/2021 SSHIELD1 ENGINEERING REVIEW Passed
08/16/2021 STEVE SHIELDS ZONING REVIEW Approved
08/16/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed