Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T21CM05931
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/29/2021 | JVINCEN1 | FIRE | REVIEW | Approved | |
08/02/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A2.0; Wall Types: Wall Type C indicates a new partial height wall up to 3'-4" top of counter. Per the ICC/ANSI Section 904, the service counter surface shall be a maximum of 36" above the floor. Please verify. |
08/02/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
08/02/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
08/02/2021 | ROBERT SHERRY | WATER | REVIEW | Completed | |
08/05/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments and provide a written response. 1. Provide complete compliance with the 2018 IECC for the lighting, Including controls (switching). 2. Verify receptacle placement and quantity in the conference room as required per NEC art 210.71. 3. Provide a complete panel schedule including load calculations. The General Notes for the lighting did not indicate. Also identify the panel on the panel schedule. Ref; 2018 IBC sec. 107.2.1, 2018 NEC, City of Tucson Commercial Plan Submittal Requirements. |
08/16/2021 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
08/16/2021 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
08/16/2021 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |